First of all I got AC again after almost a week of living in one room with a window unit. It’s gone from 81-78 in about 30 min. So it’s really not too shabby It’s just not blowing very much air. Where did my hurricane go? The duct above the stack is cool to the touch. The compressor is running fine the blower is actually spinning and blowing, which was my problem for 6 days in 100 deg heat. Replaced the old **Rheem** [ 51-24070-02 With the replacement 51-102500-01 The board is a 62-24140-04 Everything is plugged in same as the old motor. The capacitor was replaced with the same type. Just 17 years newer. **Black → COOL** **Blue → HEAT** **Yellow → FAN** **Red → M2** White → Neutral